FREE ENGINEERING REFERENCE

NEC 690 Solar Conductor Sizing
Complete Reference Tables

DC circuit ampacity, temperature correction factors, conduit fill derating, and NEC 705 busbar rule tables for solar PV design. Bookmark this page.

📊 Table 1 — Copper Conductor Ampacity at 75°C (NEC Table 310.15)

These are base ampacity values at 75°C (167°F) terminal rating. Apply temperature correction and conduit fill derating factors from Tables 2 and 3 before final selection.
AWG / kcmilTHWN-2 (75°C) — AmpacityUSE-2 / PV Wire (90°C) — AmpacityTypical Solar Use
#14 AWG15 A25 ALow-power microinverter AC circuits
#12 AWG20 A30 ASmall string circuits, AC combiner
#10 AWG30 A40 AStandard residential DC home-run runs
#8 AWG50 A55 AResidential 2-string parallel combiner
#6 AWG65 A75 ACommercial small array DC main
#4 AWG85 A95 ACommercial mid-size DC combiner runs
#2 AWG115 A130 ACommercial large array DC main
#1 AWG130 A145 ACommercial high-current DC runs
#1/0 AWG150 A170 ACommercial/utility scale DC main
#2/0 AWG175 A195 ALarge commercial DC main runs
#3/0 AWG200 A225 AUtility-scale DC collection circuits
#4/0 AWG230 A260 AUtility-scale DC collection circuits
250 kcmil255 A290 AUtility-scale DC main feeders
350 kcmil310 A350 AUtility-scale DC collection feeders
500 kcmil380 A430 AUtility-scale DC main feeders
NEC 690.8 DC Conductor Sizing Formula: I_required = Isc × strings × 1.5625 Selected conductor ampacity ≥ I_required (After applying temperature & fill derating factors)

🌡️ Table 2 — Temperature Correction Factors (NEC Table 310.15(B)(1))

Multiply conductor ampacity by the correction factor for the ambient temperature at the conductor location (e.g. attic, rooftop conduit, direct burial).
Ambient Temp (°C)Ambient Temp (°F)60°C Rated Wire75°C Rated Wire90°C Rated Wire
10°C50°F1.291.201.15
15°C59°F1.221.151.12
20°C68°F1.151.111.08
25°C77°F1.001.001.00
30°C86°F0.910.940.96
35°C95°F0.820.880.91
40°C104°F0.710.820.87
45°C113°F0.580.750.82
50°C122°F0.410.670.77
55°C131°F0.580.71
60°C140°F0.470.65
70°C158°F0.50
⚠️ Rooftop conduit in direct sun can reach 60-70°C ambient. Always use 90°C rated USE-2 or PV Wire for solar DC circuits on rooftops.

🔌 Table 3 — Conduit Fill Derating Factors (NEC Table 310.15(C)(1))

Conductors in Same ConduitDerating FactorCommon Scenario
1–3 Current-Carrying Conductors1.00 (No Derating)Standard 2-wire DC circuit
4–6 Current-Carrying Conductors0.80 (80%)Multiple string homeruns in one conduit
7–9 Current-Carrying Conductors0.70 (70%)Combiner-to-inverter trunk conduit
10–20 Current-Carrying Conductors0.50 (50%)Large commercial combiner conduit
21–30 Current-Carrying Conductors0.45 (45%)Utility-scale collection conduit
31–40 Current-Carrying Conductors0.40 (40%)Utility-scale collection conduit
41+ Current-Carrying Conductors0.35 (35%)Utility-scale multi-circuit conduit
💡 Note: Equipment grounding conductors (EGC) and grounded conductors (neutral) are NOT counted as current-carrying conductors for fill derating purposes.

⚡ Table 4 — 120% Busbar Rule Quick Reference (NEC 705.12)

Panel Bus RatingMain BreakerMax Solar Backfeed BreakerResult
100A Bus100A Main(100×1.2)−100 = 20A maxVery limited — small system only
125A Bus100A Main(125×1.2)−100 = 50A maxSuitable for ~10kW system
150A Bus150A Main(150×1.2)−150 = 30A maxLimited — MPU often needed
200A Bus200A Main(200×1.2)−200 = 40A maxStandard residential — up to ~8-10kW
225A Bus200A Main(225×1.2)−200 = 70A maxGood capacity — up to ~14kW
200A Bus150A Main(200×1.2)−150 = 90A maxExcellent — large residential systems
400A Bus400A Main(400×1.2)−400 = 80A maxCommercial — up to ~20kW AC
Max Solar Breaker = (Bus Rating × 1.20) − Main Breaker Size If result is negative or too small → Main Panel Upgrade (MPU) Required per NEC 705.12(B)(2)(3)(b)

Need These Calculations P.E. Stamped?

Our electrical engineers handle conductor sizing, SLDs, NEC 690 calculations, and 120% busbar rule compliance for your plan set — stamped and ready in 24-48 hours.

Get a P.E.-Stamped Plan Set →

Related: String Sizing Calculator · SLD Requirements Guide · 47-Point Permit Checklist